Hey I need your help.
Recently I bought a Riello NPW 2000 that output a “pseudo-sinusoidal” wave when running on battery the fact is that I read on the web that modern could do like it.
Mostly right as I found that my server (poweredge t430) is not running good with it. When unplugging the power to test the UPS something it make the PC just power off and reboot, or it make the ups in safety mode (continuous beep).
Tried disabling the PFC in IDRAC settings, as far I haven’t noticed power off issues but only safety mode issues with the UPS…
If anyone has an idea… Thank you
How many PSUs are installed in the Poweredge server? In the manual it says it could be 1 or 2 and the power per PSU could be 1100W so if it is 2 * 1100W then that could explain why the UPS has problems with it.
Only one and it’s a 750 w one. The UPS has a capacity of 900w
The load of the UPS is at its lowest even at boot